GMUD-H
DIFFERENTIAL LOW PRESSURE TRANSMITTER
The GMUD-H is a differential pressure transmitter used when air pressures above 25 mbar
are to be measured. It converts the applied pressure to a standard electrical signal,
normally 4-20 mA. The 1100 mbar absolute can be used as a barometer.
Applications are found in the climatic/ventilation sector and in filter pollution monitoring.
|
|
|

| Relative ranges: |
0...70 mbar, 0...2 bar, 0...10 bar
over-, under- or differential pressure |
| Overpressure: |
70 mbar:max 1.3 bar, 2 bar:max 4 bar, 10 bar:max 13 bar
|
| Output: |
4 to 20 mA (Two wire, load 12 Volt) |
| Accuracy sensor: |
+/- 0.2% FS hysteresis and linearity typ |
| Temperature drift: |
+/- 0.4% FS/50°C |
| Pressure media: |
Dry, non corrosive/aggressive gases, not
suited for liquids |
| Power supply: |
12...35 Vdc |
| Pressure connection: |
Studs for plastic tube 6 x 1 mm
(4 mm int. diam.) |
| Temperature range: |
0...70 °C |
| Dimensions: |
82 x 80 x 56 mm, + connections |
| Electrical connection: |
DIN 43650 |
| Options: |
RANGE10B: Other ranges, e.g. 0...100 mbar, -1...+4 bar, etc.
AV010: Voltage output 0...10 Volt (Power supply 18...30 Vdc
VO: Build in display (Power supply 17...30 Vdc
|
| Prices: |
GMUD-H |
134.90 EURO
|
| |
RANGE10B |
18.80 EURO
|
| |
AV010 |
18.40 EURO
|
| |
VO |
64.70 EURO
|
|