Home

GMUD-H

DIFFERENTIAL LOW PRESSURE TRANSMITTER

The GMUD-H is a differential pressure transmitter used when air pressures above 25 mbar are to be measured. It converts the applied pressure to a standard electrical signal, normally 4-20 mA. The 1100 mbar absolute can be used as a barometer. Applications are found in the climatic/ventilation sector and in filter pollution monitoring.

Relative ranges: 0...70 mbar, 0...2 bar, 0...10 bar over-, under- or differential pressure
Overpressure: 70 mbar:max 1.3 bar, 2 bar:max 4 bar, 10 bar:max 13 bar
Output: 4 to 20 mA (Two wire, load 12 Volt)
Accuracy sensor: +/- 0.2% FS hysteresis and linearity typ
Temperature drift: +/- 0.4% FS/50°C
Pressure media: Dry, non corrosive/aggressive gases, not suited for liquids
Power supply: 12...35 Vdc
Pressure connection: Studs for plastic tube 6 x 1 mm (4 mm int. diam.)
Temperature range: 0...70 °C
Dimensions: 82 x 80 x 56 mm, + connections
Electrical connection: DIN 43650
Options: RANGE10B: Other ranges, e.g. 0...100 mbar, -1...+4 bar, etc.
AV010: Voltage output 0...10 Volt (Power supply 18...30 Vdc
VO: Build in display (Power supply 17...30 Vdc

 

Prices: GMUD-H 134.90 EURO
  RANGE10B 18.80 EURO
  AV010 18.40 EURO
  VO 64.70 EURO